Air, ammonia, carbon dioxide and water have lower direct environmental impacts than hydrocarbons and are equally or more acceptable as replacements for fluorocarbons in suitable applications.
| Refrigerant | 170 | 290 | 600a | 600 | 601a | 601 |
| Boiling point deg C | -88.8 | -42.1 | -11.6 | -0.5 | 27.8 | 36.1 |
| Molecular mass g/mol | 30.1 | 44.1 | 58.1 | 58.1 | 72.1 | 72.1 |
| Chemical | propene | cyclopropane | neopentane | cyclopentane |
| Refrigerant | 1270 | C270 | 601b? | C601? |
| Boiling point deg C | -47.7 | -32.9 | 9.5 | 49.3 |
| Molecular mass g/mol | 42.1 | 42.1 | 72.1 | 70.1 |
The hydrocarbon (HC) refrigerants on the bottom line of the following table are substituted for the refrigerants in the first three lines:
| CFC | 502 | - | 12 | 11 | - |
| HCFC | - | 22 | 406a | - | 123 |
| HFC | - | - | 134a | - | - |
| HC | 170/290 | 290 | 290/600a | 601/601a | 601 |
Please contact a hydrocarbon refrigerant supplier for information on which of their products match the above hydrocarbon refrigerant numbers and how suitable they are as replacements in a particular application.
For centrifugal chillers, R601/601a with an electronic 38% increase in rotor speed replaces 11 and R601 with a 42% increase in rotor speed replaces 123.
In redesigned small equipment, R12 and 134a are often replaced by 600a, thinner metal and compressors with higher dimensionless specific speed. The dimensionless specific speed of the compressor is then much closer to one giving higher efficiency. The additional energy saving from higher specific speed is typically 5%.
The compatibility of hydrocarbon refrigerants with hoses and sealants is similar to that of R12.
At the temperatures occurring in refrigeration circuits, the natural hydrocarbon refrigerants, 170, 290, 600a, 600, 601a, 601 and their mixtures are very stable so they do not form gums or tars. The synthetic hydrocarbon refrigerants, 1270, C270 and C601, are unsaturated and may form gums and tars with the oil under some conditions.
Typical energy savings when hydrocarbons replace fluorocarbons and cooling capacity remains the same are:
| Capacity kW | Saving | Causes |
| Below 1 | 15% | lower pressure loss, higher specific speed and heat transfer |
| From 1 to 100 | 10% | lower pressure loss, higher heat transfer |
| Over 100 | 5% | higher heat transfer |
When heating a liquid slowly at a given pressure, the first
temperature at which large bubbles of vapour will grow is the
bubble point. Refrigerant liquid is at the bubble point for its
measured pressure if its half-full container is fully immersed in a
bath at a constant temperature below room until thermal equilibrium.
Bubble point data lines for each pressure are marked with a final
When cooling a vapour slowly at a given pressure, the first temperature at
which large drops of liquid will grow is the dew point. Dew point
data lines for each pressure are marked with a final
The difference between the dew and bubble point temperatures at a given pressure and composition is the temperature glide. Temperature glide is zero for pure substances like refrigerants 170, 290, 600a, 600, 601a and 601. The temperature glide is almost 10 K for some zeotropic mixtures like 170/290 and 290/600a. Counter or cross flow of refrigerant and fluid gives lower energy consumption than parallel flow for such glides.
The temperature difference of a superheated vapour above its dew point
temperature at a given pressure is called superheat. Two values
of superheat are given in the tables, 20 and 40 K. Each superheat line
is marked with a final
Textbooks on thermodynamics and refrigeration and air conditioning discuss the use and meaning of physical quantities in the tables like entropy and enthalpy. The tables require linear interpolation and if this is inconvenient please purchase the REFPROP program from NIST.
Hydrocarbon refrigerants are highly flammable. For the natural hydrocarbon refrigerants 170, 290, 600a, 600, 601a and 601 and their mixtures representative flammability data for initial temperature 25 deg C and pressure 101325 Pa are:
| Lower explosive limit | 34 g/kg air |
| Upper explosive limit | 170 g/kg air |
| Stochiometric mixture | 62 g/kg air |
| Flame speed | 0.4 m/s |
| Flame temperature | 2240 deg C |
| Heat of combustion | 50 MJ/kg |
Further safety data and information can be found in the literature.
Weigh cylinder or
measure liquid volume while charging. Do not exceed the charge
recommended by the refrigerant supplier. A
hydrocarbon refrigerant charge is typically one third the mass
of a fluorocarbon charge.
Do not light
cigarettes while charging refrigerant or searching for
refrigerant leaks.
Do not use
compressed air for leak testing refrigerant circuits. Use
dry nitrogen or other inert gas.
Have appropriate
equipment for extinguishing fires available while servicing
plant. A carbon dioxide fire extinguisher is
recommended as water is not safe for electrical fires.
Flameproof
electrical equipment is necessary near charges of hydrocarbon
refrigerant over 1 kg.
If the charge of
hydrocarbon refrigerant exceeds 250 g and 8 g/m^3 enclosed space,
explosion venting is necessary. Venting should keep the overpressure
from a refrigerant explosion below 2 kPa. The door windows of a motor
car bend outwards to relieve overpressure satisfactorily. The ducting
on a totally enclosed plantroom is often insufficient to relieve
overpressure. Floor to ceiling louvres to the outside with wall area
20% or greater of the plantroom floor area should be sufficient.
If a major
refrigerant release occurs, shut off the cylinder valve if charging,
evacuate the room and leave doors and windows open and ventilation fans
on. Return after refrigerant odour disappears and/or gas alarms cease.
If oil mist or
released refrigerant is ignited immediately evacuate the room and then
return with appropriate equipment to extinguish fires.
Back to Main Index
Email comments on this page to: i.maclaine-cross@unsw.edu.au (Ian Maclaine-cross)